Air-Content Test for Concrete in Ontario: A Practical Guide to Durability and Quality Control

  • Negin Amani
  • Dec 17
  • 3 min read

The freeze–thaw climate across Ontario makes durability just as critical as strength. Even well-designed concrete can deteriorate early if it lacks the right amount of entrained air.


The air content test for concrete is the primary field check engineers use to verify that fresh concrete is suitable for exterior slabs, driveways, foundations, and other elements exposed to moisture and freezing. This article explains how the test works, why it matters, and what acceptable results look like in real Ontario projects.


What Is the Air-Content Test for Fresh Concrete?


Air-Content Test for Concrete in Ontario

The air content test for fresh concrete measures the percentage of microscopic air bubbles within freshly mixed concrete. These bubbles are created by air-entraining admixtures and form a protective air-void system once the concrete hardens.


Air content is measured because:


  • It improves resistance to freeze–thaw cycles.

  • It enhances durability in areas treated with de-icing salts.

  • It affects workability and overall consistency of the mix.


Most Ontario projects use the pressure method (ASTM/CSA), while lightweight or porous aggregates require the volumetric method.


Infographic comparing Pressure vs. Volumetric methods for concrete air testing. Includes descriptions, icons, and notes on limitations.

Purpose of Air Content Test for Concrete


The purpose of air content test for concrete is straightforward:


  • Confirm durability requirements for Ontario’s freeze–thaw conditions.

  • Ensure compliance with CSA exposure classes and project specifications.

  • Balance durability, strength, and workability in fresh concrete.


When the air content meets its required range, the concrete is more likely to perform well under real service loads and weather conditions.


How the Test Is Performed On Site


The test is usually completed at the point of placement, alongside slump and temperature checks.


Typical field procedure:


  • Sample fresh concrete from the truck or pump line.

  • Fill the measuring bowl in layers and consolidate each layer.

  • Strike off the surface and secure the cover.

  • Apply pressure, stabilize the gauge, and record the air content.

  • Apply correction factors as required by the test method.


For lightweight aggregate mixes, the volumetric test is used instead of the pressure meter.


Acceptable Air Content Values in Ontario


Construction workers test concrete air content with a meter in a muddy site.

Exact values depend on the project’s exposure conditions, but practical guidelines include:


  • Exterior slabs, sidewalks, and driveways: typically around 5–8% air

  • Garage slabs and exposed parking areas: similar recommended range

  • Interior slabs without freeze–thaw exposure: lower air content or non-air-entrained mixes


The goal is not just reaching a number, but ensuring the concrete has an effective and well-distributed air-void system that supports long-term durability.


Good Field Practices for Reliable Results


Consistency matters as much as the test itself. Reliable results come from:


  • Beginning the test promptly after taking the sample.

  • Testing as close as possible to the point of placement.

  • Reviewing air content together with slump, weather, and intended exposure.

  • Ensuring the mix design and required exposure class align with CSA standards.


In higher-risk projects, advanced tools such as a Super Air Meter (SAM) may be used to assess both total air content and air-void quality for freeze–thaw performance.


Final Thoughts


The air content test for concrete is a small but essential step in protecting exterior concrete against Ontario’s harsh climate. Verifying air content during placement helps prevent scaling, cracking, and premature deterioration—saving time and cost over the structure’s lifespan.


At Parsways Inc., our engineers interpret air-content results in context. We review mix design requirements, exposure conditions, and field practices, providing clear guidance when adjustments are needed. 



FAQs


1) Why is the air content test critical for exterior concrete?

It confirms the presence of microscopic air bubbles that act as expansion chambers during freeze–thaw cycles, preventing scaling and disintegration in Ontario’s harsh climate.

2) What is the acceptable air content range?

Exterior concrete typically requires 5–8% air depending on the CSA exposure class, while interior hard-troweled slabs generally require less than 3% to avoid delamination.

3) When is the volumetric method used instead of the pressure method?

The volumetric method is mandatory for lightweight or porous aggregates, as these materials compress under pressure and cause inaccurate readings in standard Type B meters.


 
 